Công nghệ, thiết bị, nhà cung cấp, dây chuyền, máy công nghiệp trên sàn hatex.vn

Công nghệ, thiết bị, nhà cung cấp, dây chuyền, máy công nghiệp trên sàn hatex.vn

Danh mục sản phẩm
Mới

Smart 3000

Giá Liên hệ

  • Xuất xứ
  • Mã sản phẩm
  • Bảo hành
  • Hình thức thanh toán
  • Điều khoản giao hàng
  • Điều khoản đóng gói
  • Thông tin khuyến mãi

Thông tin nhà cung cấp

Thông số kỹ thuật:

DC-AC Inverter  
Continuous power 3000W + 10%
Max. Surge power 7000W ± 10%/ 50ms
Nominal DC input voltage 48 VDC
I Standby <= 1500mA
AC output voltage range At normal load adjustable: 220V – 240 VAC
Frequency 50Hz ± 1Hz
Output waveform True sine wave, distortion <= 3%
Efficiency 88%  at normal load
Power factor Cosj  >= 0.8  
Low voltage disconnect (L.V.D) Factory setting 42V ± 3%
System Manual reset by AC power switch (Over load, LVD) > 42 V ± 3%
UPS Function  
AC Input voltage range 180 – 250VAC
Frequency 50 Hz ± 1Hz
Off line UPS, transfer time 10 -12 ms
AC pass though current 13A
Search Mode  
I Standby <= 100mA
Detect power (on £ 10s, off £ 30s) 30W
Operation range 20 m and using in no special interference
DC-DC Converter  
Nominal DC input voltage 48 VDC
DC  operating range 42 – 58 VDC
DC output voltage 12V  ± 3%
Max.  DC output current 20A
DC protection output >= 20 A (Electronic protection)
Battery Charger  
Charge type  Sealed gel /AGM Flooded Lead Acid
2-Step charger Boost charge 56 -57V 59 - 60V
Float charge (Constant Vol.) 55.2V ± 0.5V 55.2V ± 0.5V
Recharge 50.4 ± 0.5V 53.2V ± 0.5V
Max. Charging current of
AC grid/ generator and DC solar/ wind, hydro, add.
20A/ 50A/50A
Protection  
Overload AC AC output voltage will be decreased
Over temperature, L.V.D AC/DC power cut off
Reverse polarity DC fuse protected
Charging Sources – Led lighting  
Solar - active Green
Wind/ Hydro/ Add - active Green (lighting I charge >= 5A)
Grid - active Green
Charging - active Orange
Battery level monitor  
Full 56 -57V / 59 - 60V /Green
Normal >= 49.2V ± 2%  /  Green
Low >= 44V ± 2%  / Orange
Empty <=42V ± 2%  /  Red
Meter/ Fan/ Fuse & others  
DC voltage meter 75V
AC voltage meter 300V
AC/DC charging current meter 20A/50A/50A – At 48VDC
DC fuse input/ DC Breaker/AC Breaker 150A/100A /15A
Fan  7, Thermally controlled
Climatic condition 10 – 45°C
Dimension (L x W x H) mm 530 x 424 x 800
Weight Appr. 60kgs
Regulations  
EC compliance EN60742, 1995; EN50075, 1990; EN55014-1; EN55014-2; EN 61000-3-2; EN61000-3-3; EN50091-1-2,1996; EN60950
EC Directives Low-voltage